March 29(Friday) , 2024

Products / 产品资讯

username:
password:

Tower

Position:Home > Products > Tower > Hpower Series [10/400KVA]

Hpower  Series

·Description

HPower featured 3-in 3-out UPS power is specially designed for critical medium and large systems, such as data processing centers, communications systems, and enterprise equipments. It provides a stable power environment and reliable power protection to meet the requirements of high reliability and high-power UPS of the users. The innovative design makes this series with unparalleled reliability and high-performances. The high input power factor and low input current distortion rate make it the green and environmental-protected product. The high efficiency grantee the energy saving efficiency. Advanced control technology enable up to 6 set directly run in parallel. UPS monitoring software can achieve communication between the UPS and the PC through the RS232 interface and allow users to understand the contents of the working status and the history of the UPS. Optional SNMP card makes network remote monitoring and management possible, which is truly unattended. Hpower Series UPS is your best choice!

·Application

Servers, data networks and internet service provider in telecommunication, finance, insurance, government, transportation and medical labs.

·Features

■ SPWM pulse width modulation IGBT power module output isolation transformer (optional), ensuring that the output is unaffected by power grid fluctuations and noise interference;
■ DSP all-digital control all processes of rectifier, inverter, charge and discharge power conversion;
■ Digital circulation technology, small circulation, and raise the reliability of the overall parallel system;
■ Wide input voltage and frequency range, adapting to harsh grid environment and accessible to generator;
■ The input power factor up to 0.99, the input harmonic current of less than 3%, the whole greater than 95% efficiency, environmental-protection, energy-efficient;
■ Under-voltage/ over-voltage protection, overload protection, short circuit protection, over temperature protection, battery low voltage alarm/protection, battery over charge/discharge protection, and so on;
■ Full Frontal maintenance, supporting up and down into the line way, saving installation space;
■ Modular design for subsystem easy on-site maintenance;
■ Internal manual maintenance bypass further improve the reliability of load continuous operation up to 200,000 hours, MTBF, MTTR 30 minutes;
■ System fan take redundancy design, and greatly improve the reliability of the system;
■ Standard input anti-lightening board (optional) and enhance the anti-jamming capability;
■ Intelligent battery management (ABM) extends battery life and reduces the maintenance;
■ State-of-the-art automatic constant current and voltage conversion charging technology maximize the activation of the battery charger to save time, thus extending the service life of the battery;
■ High operating efficiency reduces the running costs of the machine, the design of this series allows the user to select the line and the economy / bypass operation mode, economy / bypass operating mode operating efficiency can reach 99%, thus greatly reducing operating costs and extending battery life;
■ Insert and machine module (optional) can be up to six run in parallel ,which increases the reliability and scalability of the system ;
■ Self-diagnostic function avoid UPS hazards that may lead to the risk of failure;
■ Intelligent system self-diagnostics program, a rich record of failure, capacity history of storage space;
■ Friendly interface design, configuration, with large-screen LCD touch screen and control the keyboard, ensuring users to accurately display the UPS work environment and working conditions;
■ Through RS232, RS485 interfaces with the monitoring software users being able to communicate with a computer. The various parameters of the UPS can be displayed on communication interfaces;
■ The configuration of the SNMP card and monitoring software, using TCP/IP, SNMP, HTTP, TFTP, through the WEB browser, to achieve in the Internet/ Intranet remote monitoring, real-time status query, information management, remote control, parameters settings, user managements, historical data query comprehensive monitoring and management functions, and can send short message or Email to users to alarm through mobile phones or system administrators, support for the operating systems: Windows 7, Unix, Linux etc.

·Technical Specifications


Model

HP10

HP15

HP20

HP30

HP40

HP60

HP80

HP100

HP120

HP160

HP200

HP400

Capacity

10KVA

15KVA

20KVA

30KVA

40KVA

60KVA

80KVA

100KVA

120KVA

160KVA

200KVA

400KVA

Input

Voltage

380/400/415VAC(228518VAC)

Voltage Range

-40%25% (input voltage from -20%-40% linear decline, power from 100%-70% linear decline)

Frequency

4070Hz

Power Factor

>0.99

Soft Start

60s

Current Distortion

<3%

Max Input Current

15

23

30

45

60

90

120

150

180

240

300

600

Bypass

Voltage

380/400/415VAC

Voltage Range

-20% +15%

Frequency

50/60Hz

Frequency Range

±3Hz(±15% adjustable)

Inverter/Bypass Transfer Time

Synchronous switching: ≤ 1ms; uninterrupted switching: ≤ 10ms

Overload

<135% long-term work135%150% maintain 1minute then shutdown>150% maintain 300ms then shutdown

Output

Voltage

380/400/415VAC

Voltage accuracy

±1%(load balancing), ±1.5%(unbalanced load)

Frequency

50/60Hz±0.01%

Voltage distortion rate

THD<1% (linear load), the THD<3% (nonlinear)

Phase Voltage

220V

Peak

3:1

Waveform

Sine Wave

Waveform Distortion

±1%

Three Phase of Precisions

120°± 0.5°

Power Factor

0.9

Steady-state voltage Stability

±0.5% (Load balancing)

Transient Voltage Response

In 20ms, restored to ±1% output voltage

Overload

105% long-term work110%/125%/150% maintain 1hour/10minutes /1minute then switch to bypass>150% maintain 200ms then switch to bypass

Battery Power Switching Time

0ms

Bypass Inverter Time

0ms

MTBF

200,000hrs

Dynamic Voltage Transients

<5% (0100% load)

Voltage Unbalance (100% load unbalancing)

±3%

Frequency Tracking Rate

0.1 Hz/s-5Hz/sadjustable

Battery

Type

Sealed maintenance free lead acid battery

Voltage

±240VDC (3244 can be set)

Charging Settings

Intelligent dynamic adjustment; Amperage is20%*System Capacity/Voltage

Voltage Stability

±1%

System

System Efficiency

Normal Mode: 95%Economic Mode: 98%

Battery Mode Efficiency

>96%

Display

LCD+LED + keyboard

Display

Wiring

Up and down wiring

Optional

SNMP network communication card, Parallel component , lightning protection module, battery temperature compensator, message alarm, dust-proof net,LBS

Environment

Working Temperature

040

Storage Temperature

-10℃~40

Relative Humidity

095%( non-condensing)

Altitude

≤1000 m>1000 mde-rating according to GB/T 3859.2

Noise(dB)

<55dB

Communication

Ports

RS232RS485,contracts,optional SNMP card, Generator interface

Control Board

EPO

Protection

EMI

IEC62040-2

EMS

IEC61000-4-2(ESD) IEC61000-4-3(RS)

IEC61000-4-4 (EFT) IEC61000-4-5 (Surge)

Insulation Resistance

>2M (500VDC)

Dielectric Strength

(Input and output to ground) 2820Vdc. The leakage current is less than 3.5mA 1 minute without flashover

Surge Protection

Complied with VI of IEC60664-1, can withstand 1.2/50us +8 / 20us mixed wave capacity of not less than 6KV/3KA

Protection Level

IP21

Standard

Safety standard

EN62040-1

EMC

EN62040-2EN61000-4-2EN61000-4-3EN61000-4-4EN61000-4-5EN61000-4-6

Produce

YD/T1095-2018

Physical Feature

Weight(kg)

(internal/external)

87/43

97.5/46

90/46

107/60

116

170

210

210

266

305

350

810

Size(W*D*H, mm)

540*690*1100

Built-in type

540*690*1100

Built-in type

540*764

*1100

600*980

*950

600*980

*1150

600*980

*1400

650*960

*1600

1300*1100

*2000

280*731*668

External type

320*781*788

External type

Products shall be subject to any changes without additional notices. The pictures are for reference only. Please adhere to the original products in case of any mistake!