Data center MP series
·Description
MP Series modular UPS is designed to meet with the higher demands of the power system and the products with high reliability. The system uses the original double conversion structures of 3-in and 3-out; all of the power semiconductor devices are made of imported integrated module, which greatly improves the reliability of the system. The power supply system consists of multiple independent power modules in parallel, which can make the main synchronizationand N + X parallel redundant backup run smoothly, and greatly improve the overall reliability of the system; of which the power system has perfect self-testing and protection functions, and the big screen can possess with touch screen LCD graphical user interface, intelligent "man - machine" dialogue menu and remote monitoring and regulatory functions. The power supply system rectifier and inverter use the industry's most advanced technologies and can achieve 96%efficiency of the system, which make it the most efficient and more energy-saving than the lowest power density products. It is highly cost-effective.
(1)STS
STS module is mainly used for fast switching between the inverter output and the AC bypass power to comprehensively improve the security and reliability of supply. It receives two sets of AC input, and selects a group of output. When working online, STS connects inverter output of power module to the system output. If the power module in a particular time,it can not provide enough voltage, STS will immediately switch to bypass the power supply.
Adopted foreign advanced high-power thyristors, STS can achieve zero switching, at the same time it has a very strong impact of resistance and ability to withstand short circuit, so that the reliability and stabilityof the system are greatly enhanced. It includes: the internal self-testing function; interlock function; the abnormal system output protection function; momentary power failure protection function; output overload and short circuit protection. With RS485 interface, integrated MODBUS communication protocol, standard input and output dry point card. The entire static switch bypass supports online hot-swappable line replacement without affecting the power supply to the load. It also has UART communication functions, which can communicate with system monitor and modular units, send and receive orders and all kinds of alarm information at any time.
(2)System Monitoring
System monitoring in the above of cabinet, users can check the working status of the system, the query parameters and event information through display and the operator panel. After the system is installed, all operating system can be completed on the operation panel of the monitor. The acquisition of system data is completed by a 32bitdigital processor. Display is 210*160 with touch LCD, which enables touch and press operation to meet with different operating habits, and it is easy and flexible. It also provides RS232, RS485 communication interface and standard multiple input and output dry point card. With optional TCP / IP cards and GSM SMS, the alarm remote network monitoring can be achieved. The system monitor is divided into three regions: the status indicator area, the data display area, the key operating area. Status indicator area provide a simple system status information through the different states of the LED to the users; LCD data display provide users with detailed system status information through the LCD display, and the system monitoring display four operator interfaces: SYSTEM, EVENTS,UPSMODULE and SETUP. The system provides a multilingual display, such as the Sino-British, which is a friendly user interface; all operations have achieved a graphical interface, simple and straightforward. When user operation buttons, the LCD screen has a corresponding information display, allowing users to have excellent operating experience.
(3)Power Module
Power modules use a multi-system online double conversion technology to transform after the main rectifier, filter, regulator for DC, the DC after level inverter circuit powered by a separate digital charger to charge the battery pack and intelligent management, post-inverter circuit sine wave modulation circuit for a high efficiency of the third order, then DC re inverter AC load regulator, thus providing frequent, continuous, and reliable power. AC input for the three-phase mains, output DC ± 240V dedicated battery pack charge, which is a three-phase output AC sine wave AC voltage.
Modules have self-diagnosis, input over-voltage/low voltage protection, output over-voltage/low voltage protection, short protection, over-temperature protection,etc.
Module have intelligent communicate interfaces which can communicate with system monitors and send and receive orders and alarms.
Module have full UPS functions,integrated rectifier, inverter, charge, and control in one. Module can work normally without external synchronization control signal or other means of control, which reduce the bottleneck of the system and improve its reliability.
Module dustproof design: IP protection class IP20/IP21(optional), the positive protective surface mesh and filter available online to disassemble and clean. All board sprays are specially painted, which improve the environmental adaptability, and make it possible to be used in harsh environments.
·Applications
It can be applied in servers, data networksand internet service providers in telecommunication, finance, insurance, government, transportation and medical labs.
·Features
MP Series modular UPS system not only has the characteristics of machine redundancy that can completely replace the traditional 1 +1, 2 +1 and systems, and possess the traditional and unmatched online hot swap functions. Both reliability and availability are much higher than the traditional machine system. At the same time, it is a "green power" program, with a high input power factor ,low harmonic distortions and high efficiency, high stability and reliability advantages, with powerful monitoring software and comprehensive communications interfaces. It is suitable to be used in data center, especially telecommunications and the financial industries.
■ Redundancy: MP is a 3-in and 3-out redundant modular UP, which is composed of STS module, system monitoring module and 1 to N power modules in parallel. System capacity are100KVA、150KVA、200KVA、250KVA、300KVA、400KVA、500KVA、600KVA with power module of10KVA、15KVA、20KVA、25KVA、30KVA、40KVA、50KVA seven power ranges .Users can choose freely according to the size of the load, the power module is free to expand, replace the hot-swap mode; MP system uses the power module of average burden on system load from control technology, an array of parallel, multi-level distributed, parallel modules are built-in redundancy intelligent independent individual, without parallel system centralized control system monitoring, non-bottleneck, and the performance of which is reliable. Failure of any module (including system monitoring) the MP system redundancy design will be fully effective, comprehensive protection for the normal operation of the equipment, achieving the biggest degree of fault redundancy, while the user can be selected more than once redundant fault tolerance ;
■ Scalability: MP system architecture is highly flexible and redundant scalable system with N + X redundancy, according to the needs of the user ,upgraded online capacity expansion. Thedesigning concept of the power module in the system can easily be removed and installed without affecting system operation and output, and the demand expansion "of the investment planning, allowing users to" dynamic growth ", with business development to meet with the needsof expanding, but can also reduce the initial acquisition costs;
■ Reliability: power module configuration dual DSP controller, an independent control module, of which there is no point of failure risks. Rectifier, inverter, charge, discharge all DSP digital control. IGBT module instead of discrete devices, having a greater current carrying capacity and smaller power of consumption, which greatly improves the efficiency and reliability of the power modules and systems;
■ Availability: MP systems have the super parallel functions, which is the leading representative of the high-end UPS technologies, and the average time to failure values (MTBF) is 1.5 times than that of traditional UPS, the average major failures value (MTBCF) is 3 times than that of the traditional UPS systems, mean time to repair time value (MTTR) is only five minutes in the system under normal operating conditions;
■ Flexibility: the MP system's battery pack (± 240V) shared by all UPS modules in the system (including the charge and discharge). Can be a user needs to use a battery or battery in parallel to increase the system standby time. MP system uses the flexible battery access mode, reducing the number of battery voltage and improving the service life of the battery pack;
■ Safety: the MP system power module uses a three-phase five-wire input. State-of-the-art high-frequency control technology enables the MP system to meet the safety requirements of all kinds of key equipment for the zero-to-ground voltage line operation;
■ Environmental Protection: MP system PFC circuit uses advanced active average current control technology, the input current total harmonic distortion (THDI) only 3%, while unit input power factor PF> 0.99. Linear load conditions, which greatly reduce the power grid pollution effectively reduce grid load and power consumption, machine efficiency up to 96% energy savings;
■ Management: MP system built-in power analysis and a variety of communication interfaces with intelligent monitoring software, two-way interactive communication through a variety of communication interface with the administrator, the administrator at any time remote monitoring system, some unusual phenomenon pretreatment, so that the system is always smooth and reliable operation; inside each module to set up a dedicated charging rectifier, high reliability, high-frequency noise, avoid high-frequency wave impact on the battery life; avoid battery overheating charging and extended battery life; system monitoring the battery pack average float conversion and limiting charge; the average float voltage and the charging current limit value can be set; with temperature compensation and self-discharge detection function;
■ Maintenance: MP system using a state-of-the-art hot-swappable UPS module technology, monomer module can any online into or out of a parallel unit, without blackouts operation. The online parallel system maintenance and the operation can be carried out without special instruments and techniques.
·Technical Specifications
Model |
MP60 |
MP90 |
MP100 |
MP120 |
MP150 |
MP200 |
MP400 |
Capacity |
60KVA |
90KVA |
100KVA |
120KVA |
150KVA |
200KVA |
400KVA |
Input |
|||||||
Voltage |
380/400/415VAC |
||||||
Voltage Range |
228V~478VAC |
||||||
Frequency Range |
40~70Hz |
||||||
Soft Start |
60s |
||||||
Power Factor |
≥0.99 |
||||||
Current Distortion |
THDi <3%(100% linear load) |
||||||
Bypass |
|||||||
Voltage |
380/400/415VAC |
||||||
Voltage Range |
-20%~+15% |
||||||
Frequency |
50/60Hz |
||||||
Frequency Tracking Range |
±1Hz, ±3Hz, ±5Hz |
||||||
Inverter/Bypass Transfer Time |
Synchronous switching: ≤ 1ms; uninterrupted switching: ≤ 10ms |
||||||
Overload |
<135% long-term operation;135%~150% switch off 6 minutes later; >150% switch off 300ms later |
||||||
Output |
|||||||
Voltage |
380/400/415VAC |
||||||
Voltage Accuracy |
±1% |
||||||
Frequency |
50/60Hz±0.01 |
||||||
Voltage Distortion |
Linear load <1%, non-linear load <3% |
||||||
Phase Voltage |
220V |
||||||
Peak |
3:1 |
||||||
Waveform |
Sine Wave |
||||||
Waveform Distortion |
±1% |
||||||
Three-phase Phase Accuracy |
120°±0.5° |
||||||
Power Factor |
0.9 |
||||||
Steady-state Voltage Stability |
±0.5% (Load balancing) |
||||||
Transient Voltage Response |
Restore to output voltage steady-state value ±1% within 20ms |
||||||
Overload |
110% long-term work;125%/150% maintain 10minutes /1minute then switch to bypass;>150% maintain 200ms then switch to bypass |
||||||
Grid/Battery Switch Time |
0ms |
||||||
Bypass/Inverter Switch Time |
Synchronous switch ≤1ms |
||||||
MTBF |
≥400,000 hours |
||||||
Dynamic Voltage Transients |
5% (0~100% load) |
||||||
Frequency Tracking Rates |
0.5-5Hz/s,adjustable |
||||||
Voltage Unbalance (100% Load Unbalancing) |
±3% |
||||||
Battery |
|||||||
Type |
Sealed maintenance free lead acid battery/lithium battery |
||||||
Voltage |
± 240VDC (32~44 can be set) |
||||||
Charging Power |
Intelligent dynamic adjustment; Amperage is (20%*System Capacity)/Voltage |
||||||
Charging Power Accuracy |
±1% |
||||||
System |
|||||||
Efficiency |
Normal Mode:>96%; Economic Mode:>99% |
||||||
Battery Mode Efficiency |
>96% |
||||||
Display |
LCD+LED, Touch screen + keyboard |
||||||
Protection Level |
IP20/IP21(optional) |
||||||
Interface |
RS232, RS485, USB, programmable stem node, optional SNMP card, EPO, dynamo interface and AS400 card |
||||||
Wiring |
Up and down |
||||||
Optional |
SNMP network communication card, anti-thunder module, parallel-operation components, LBS, battery temperature compensator, SMS alarm, dust screen and shock-proof components |
||||||
Environment |
|||||||
Operation Temperature |
0~40℃ |
||||||
Storage Temperature |
-25℃~70℃ |
||||||
Relative humidity |
0~95%(non-condensing) |
||||||
Noise(dB) |
<55dB |
||||||
Standard |
|||||||
Safety standard |
EN62040-1 |
||||||
EMC |
EN62040-2,EN61000-4-2,EN61000-4-3,EN61000-4-4,EN61000-4-5,EN61000-4-6 |
||||||
Produce |
YD/T2165-2017 |
||||||
Physical characteristics |
|||||||
Weight(kg) |
3module Cabinet:105KG (MP30 MP45 MP60) |
||||||
6 module Cabinet:145KG (MP60 MP90 MP120) |
|||||||
10 module Cabinet:179KG (MP100 MP150 MP200) |
|||||||
Size(W*D*H, mm) |
3 module Cabinet:600*900*1100 (MP30 MP45 MP60) |
||||||
6 module Cabinet:600*900*1600 (MP60 MP90 MP120) |
|||||||
10 module Cabinet:600*900*2000 (MP100 MP150 MP200) |
Model |
MP250 |
MP300 |
MP500 |
MP600 |
MP750 |
MP900 |
MP1200 |
MP1500 |
Capacity |
250KVA |
300KVA |
500KVA |
600KVA |
750KVA |
900KVA |
1200KVA |
1500KVA |
Input |
||||||||
Voltage |
380/400/415VAC |
|||||||
Voltage Range |
228V~478VAC |
|||||||
Frequency Range |
40~70Hz |
|||||||
Soft Start |
60s |
|||||||
Power Factor |
>0.99 |
|||||||
Current distortion |
THDi <3%(100% linear load) |
|||||||
Bypass |
||||||||
Voltage |
380/400/415VAC |
|||||||
Voltage Range |
Settable , default: -20%~+15% Upper limit: +10%,+15%,+20%,+25% Lower limit: -10%,-15%,-20%,-30%,-40% |
|||||||
Frequency |
50/60Hz |
|||||||
Frequency Tracking Range |
Settable,±1Hz,±3Hz,±5Hz |
|||||||
Inverter/Bypass Transfer Time |
Synchronous switching: ≤ 1ms; uninterrupted switching: ≤ 10ms |
|||||||
Overload |
<135% long-term operation; 135%~150% switch off 6 minutes later; >150% switch off 300ms later |
|||||||
Output |
||||||||
Voltage |
380/400/415VAC |
|||||||
Voltage Accuracy |
±1% |
|||||||
Frequency |
50/60Hz±0.1% |
|||||||
Voltage Distortion |
Linear load <1%, Non-linear load <3% |
|||||||
Phase Voltage |
220V |
|||||||
Peak |
3:1 |
|||||||
Waveform |
Sine Wave |
|||||||
Waveform Distortion |
±1% |
|||||||
Three-phase Phase Accuracy |
120°±0.5° |
|||||||
Power Factor |
1 |
0.9 |
||||||
Steady-state Voltage Stability |
±0.5% (Load balancing) |
|||||||
Transient Voltage Response |
Restore to output voltage steady-state value ±1% within 20ms |
|||||||
Overload |
110% long-term work;125%/150% maintain 10minutes /1minute then switch to bypass;>150% maintain 200ms then switch to bypass |
|||||||
Grid/Battery Switch Time |
0ms |
|||||||
Bypass/Inverter Switch Time |
Synchronous switch:≤1ms |
|||||||
MTBF |
≥400,000 hours |
|||||||
Output Dynamic Response |
<5% (20%~80%~20% step load) |
|||||||
Dynamic Recovery Time |
<20ms(0%~100%~0 step load) |
|||||||
Frequency Tracking Range |
±3.5Hz/s(±0.5Hz/s~±5Hz/s adjustable) |
|||||||
Frequency Tracking Rate |
0.5Hz/s(0.5Hz/s~3Hz/s adjustable) |
|||||||
Voltage Unbalance (100% Load Unbalancing) |
±3% |
|||||||
Battery |
||||||||
Type |
Sealed maintenance free lead acid battery/lithium battery |
|||||||
Voltage |
±240VDC (32~44 can be set) |
|||||||
Charging Current |
Intelligent dynamic adjustment; Amperage is (20%*System Capacity)/Voltage |
|||||||
Charging Power Accuracy |
±1% |
|||||||
System |
||||||||
Efficiency |
Normal Mode:>96%; Economic Mode:>99% |
|||||||
Battery Mode Efficiency |
>96% |
|||||||
Display |
LCD+LED, 10.4 inches touch screen |
|||||||
Protection Level |
IP20/ IP21(selectable) |
|||||||
Interface |
RS232, RS485, USB, programmable stem node, optional SNMP card, EPO, dynamo interface and AS400 card |
|||||||
Wiring |
Up and down |
|||||||
Optional |
SNMP network communication card, anti-thunder module, parallel-operation components, LBS, battery temperature compensator, SMS alarm, dust screen and shock-proof components |
|||||||
Environment |
||||||||
Operation Temperature |
0~40℃ |
|||||||
Storage Temperature |
-25℃~70℃ |
|||||||
Relative Humidity |
0~95%(non-condensing) |
|||||||
Height |
≤1000m, de-rating 1% for every increase of 100 meters from 1000 to2000 |
|||||||
Noise(dB) |
<65dB for 100% loading, <62% for 45% loading |
|||||||
Standard |
||||||||
Safety Standard |
EN62040-1 |
|||||||
EMC |
EN62040-2,EN61000-4-2,EN61000-4-3,EN61000-4-4,EN61000-4-5,EN61000-4-6 |
|||||||
Produce |
YD/T2165-2017 |
|||||||
Physical Characteristics |
||||||||
Weight(kg) |
6 module Cabinet:178KG (MP150 MP180) |
|||||||
10 module Cabinet:242KG (MP250 MP300) |
||||||||
10 module Cabinet:450KG (MP400 MP500) |
||||||||
20 module Cabinet:660KG (MP500 MP600) |
||||||||
Size(W*D*H, mm) |
6 module Cabinet:600*1100*1600 (MP150 MP180) |
|||||||
10 module Cabinet:600*1100*2000 (MP250 MP300) |
||||||||
10 module Cabinet:1300*1100*2000 (MP400 MP500) |
||||||||
20-module cabinet:2000*1050*2000 (MP500 MP600) |
Module Model |
M10 |
M15 |
M20 |
M25 |
M30 |
M40 |
M50 |
||
Capacity |
10KVA |
15KVA |
20KVA |
25KVA |
30KVA |
40KVA |
50KVA |
||
Number(Up to) |
10 |
20 |
10 |
||||||
Input |
±240VDC (32~44 can be set) |
||||||||
Input/ Output Access |
3-IN and 3-out |
||||||||
Size(W*D*H, mm) |
440*590*134 |
460*790*134 |
510*700*178 |
||||||
Weight(kg) |
20kg |
21kg |
22kg |
32kg |
34kg |
44kg |
45kg |
||
Description |
Each module can supply 2kva charging power |
Each module can supply 3kva charging power |
Each module can supply 4kva charging power |
Each module can supply 5kva charging power |
Each module can supply 6kva charging power |
Each module can supply 8kva charging power |
Each module can supply 10kva charging power |
||
Input Power Factor |
>0.99 |
||||||||
Overload |
Comply with system requirements |
||||||||
THD |
<1%(Linear load),<3%(Non-linear loads) |